SWITCH GEARS

 


SWITCH GEARS

Ø It is an assembly of main and auxiliary switching apparatus for operation, regulation, protection or other control of electrical installation.

Ø It is a means of isolating the supply, protecting against excess current and cutting off the current if a serious earth fault occurs.

 

Purpose of Switch Gears

i)       Isolation - Is to provide a mean of isolating the final circuits and the mains supply

ii)   Protection against excess current – Is to provide means of cutting off the current if a serious earth fault occurs.

iii)   Means cutting off electrical supply to a circuit or item of equipment in order to ensure that the safety of those working on the equipment by making dead those parts which are live in normal service.

 

Types of Switchgears

a)     Fuse

b)     Circuit breakers

c)      Change over switch

d)    Isolator

e)      Main Switch

 

(A)       FUSES

A fuse is defined as “A device for opening a circuit by means of a conductor designed to melt when an excess current flows. There are three types of fuses:

1.    Rewirable fuse

2.    Cartridge fuse

3.    High breaking capacity (H.B.C.) fuse, formerly known as High rupturing capacity (H.R.C.) fuse.

 

 

Rewirable Fuse

The rewirable fuse consists of a fuse holder, a fuse element and a fuse carrier. The base and carrier are made of either Bakelite or porcelain.

The fuse element is connected between the terminals of the bridge. An asbestos tube, or pad, is generally fitted in the fuse to minimize the effect of arcing when the fuse element melts. This type of fuse is termed “semi-enclosed fuse” to distinguish it from the old type of fuse which consisted simply of a piece of wire connected between two terminals.

 

The following is the example of approximately sizes of tinned copper wire to be used for element in semi-enclosed fuses.

Standard wire gauge

Current rating

0.15mm

3A

0.2mm

5A

0.35mm

10A

0.50mm

15A

0.60mm

20A

0.75mm

25A

0.85mm

30a

1.25mm

45A

1.53mm

60A

1.80mm

80A

2.00mm

100A

 

The current rating: is the current which the fuse element will carry continuously without deterioration or breaking.

The fusing current: is the minimum current at which the fuse element will melt. This is approximately twice the current rating of the fuse element

The Fusing Factor: - In order to classify protective devices, it is important to know their circuit breaking and fusing performance. For fuses this is achieved by for by using the fusing factor. Fusing factor is the ratio of fusing current to Current Rating.

Fusing Factor = Fusing Current

                          Current Rating

 (Fusing factor of Rewirable fuse is 2)

 

Advantages of rewirable fuse

1.    Cheap

2.    Can easily be seen when the fuse is blown

3.    Easy to replace fuse element

4.    No mechanical moving parts

Disadvantages

1.    Fuse element deteriorate in use

2.    An incompetent person can replace an incorrect size of the fuse element thus, defeating the purpose of fuse.

Note: The fuse must be capable of protecting the smallest conductor in the circuit. 

3.    Lacking in discrimination. The rewirable is not capable of discriminating between a momentary high starting current and a continuous fault current.

4.    Easily damaged, particularly with short circuit currents.

 

Cartridge Fuse

This type of fuse is commonly used with the 13A plug used on the domestic power circuits. The fuse element is contained in porcelain or glass tube fitted with two connecting metal caps, to which the fuse element is attached. The cartridge fuse has a fusing factor of 1.6-1.8

 

 

The following is the colour code table for cartridge fuses:

Current

Colour

5A

White

13A

Brown

15A

Blue

20A

Yellow

30A

Red

45A

Green

60A

Purple

 

Advantages of Cartridge fuse

·       No mechanical moving parts

·       Declared rating is accurate

·       The element does not weaken with age

·       Small physical size and no external arcing.

·       Low fusing factor.

·       Easy to replace.

Disadvantages of cartridge fuse

·       More expensive than rewirable fuses.

·       Can be replaced with an incorrect size fuse

·       Not possible to see if the fuse has blown.

·       Require a stock of spare fuses to be kept.

 

High Breaking Capacity Fuse

This type of fuse is designed to protect against heavy overloads and is capable of opening a circuit under short circuit conditions without damaging the surrounding equipment.  It is a very fast acting fuse and discriminates between a starting surge and an overload current.

A high breaking capacity fuse consists of the followings:

1.    Porcelain/Ceramic tube

2.    Silver element

3.    Indicating element which ignites powder under the label to show when the fuse element has opened.

4.    End caps

5.    Silica (fine sand) filling used to quench the arc.

Advantages of High breaking capacity fuse

·       No mechanical moving parts

·       The element does not weaken with age

·       Operation is very rapid under fault conditions

·       It is difficult to interchange the cartridge, since different ratings are made to different physical sizes.

Disadvantages of High breaking capacity fuse

·       Very expensive than cartridge fuses and rewirable fuses.

·       Stocks of these spares are costly and take up space.

·       Care must be taken when replacing them in order to ensure that the replacement fuse has the same rating and also the same characteristics as the fuse being replaced.

Note: The fuses must always be connected to the phase conductor and never be connected in the neutral conductor.

 

(B) CIRCUIT BREAKERS

A circuit breaker is defined as “a mechanical device for making and breaking an electric circuit both, under normal and abnormal conditions, such as short circuit, over loading and earth leakage faults, the circuit being broken automatically”.

Under normal condition the circuit breaker is generally opened and closed by hand (manually), but is automatically opened under fault conditions.

There are two types of circuit breaker:

1.    Miniature circuit breaker (MCB)

2.    Earth leakage circuit breaker (ELCB)

 

Miniature Circuit Breaker (MCB)

Miniature circuit breakers are used as an alternative to fuse. They are available in distribution board units for final sub-circuits protection, and they have several advantages:

1.    It can be reset or closed easily

2.    It gives a close degree of small over current protection (The tripping factor is 1.1)

3.    MCB is much more sensitive to over current than fuse.

4.    Handling MCB is more electrically safe than fuse.

5.    MCB tends to give much better overall protection against fire and shock risks than can be obtained with the use of fuses.

Working Principle: There are two arrangement of operation of miniature circuit breaker:

i)                   Due to Thermal effect of over current - Is achieved with a bimetallic strip when continuous over current flows through MCB, the bimetallic strip is heated and deflects by bending and releases mechanical latch which then opens the miniature circuit breaker contacts.

ii)                Due to Electromagnetic effect of over current - Is achieved during short circuit condition. A sudden rising of electric current, causes electromechanical displacement of plunger associated with tripping coil or solenoid of MCB. The plunger strikes the trip lever causing immediate release of latch mechanism thus open the circuit breaker contacts. Therefore, a bimetal provides protection against over load current and an electromagnet provides protection against short-circuit current.

Electromagnetically operated over current release

 

Operating Mechanism of Miniature Circuit Breaker

The Operating Mechanism of Miniature Circuit Breaker provides the means of manual opening and closing operation of miniature circuit breaker. It has three-positions “ON,” “OFF,” and “TRIPPED”. The external switching latch can be in the “TRIPPED” position, if the MCB is tripped due to over-current. When manually switch off the MCB, the switching latch will be in “OFF” position. In close condition of MCB, the switch is positioned at “ON”. By observing the positions of the switching latch one can determine the condition of MCB whether it is closed, tripped or manually switched off.

Disadvantages:

1.    It is expensive than fuse

2.    There is a tendency for the tripping mechanism to stick in operation after a long period of operating.

 

Earth Leakage Circuit Breakers (ELCB)

These falls into two classes:

1.    Voltage operated Earth leakage circuit breakers

2.    Current operated Earth leakage circuit breakers

 

Voltage operated type:

The basic circuit consists of a coil connected between the metal frame work of the installation and the general mass of earth as shown in the figure above.

Voltage operated units are designed to be directly responsive to fault voltage which appears on protected metal work, which happens when the earth path resistance is high. (Ohm’s law applies. Where V = IR: I is the amount of fault current, R is the resistance of the earth path)

 

Principle Operation

Voltage operated type are actuated by rise of potential of the protected metal work caused by earth leakage current. When an earth leakage current flows, the potential of the protected metal work will rise because of the impedance of the earth fault loop path. This potential causes a current to flow through the trip coil of E.L.C.B. and so to earth via the reference earth electrode. The maximum p.d. required to actuate the ELCB must not exceed 40V so that the danger of shock is reduced to minimum.

Test switch is required so that the unit can be tested at frequent intervals to make sure that the continuity of the earth path is maintained and also to ensure that the protection of the unit is satisfactory.

A high resistance resistor is also connected in the circuit to limit the test current.

Current operated type:

Current operated are actuated by excessive earth leakage current. As shown in the diagram below, there is no direct connection between the earthing lead and the ELCB.  A ‘core balance’ transformer is being used to detect the presence of earth leakage currents.

Under normal condition the current flowing in the live conductor equals the current returning from neutral conductor.                                                                             The two primary coils of the transformer are wound with opposite polarity so, under normal conditions their magnetic effects balance each other and no voltage is induced in the secondary coil. When an earth fault occurs, the fault current returns via the earth loop path instead of the neutral conductor, thus the current taken from the live conductor exceeds the current returned to the neutral conductor. This disturbs the balance between the magnetic effects of the two primary coils and the magnetic flux is set up in the core thus inducing a voltage in the secondary coil which in turn operates the tripping (operating) coil relay.

 

Application:

1.    Voltage operated type: Used in domestic and small industrial installations to give protection against shock risk where a good earth cannot be obtained (because of rocky or dry sub soil)

2.    Current operated type: Useful in large installations where very heavy fault currents would flow before the over current device is operated, thereby creating a serious fire risk.

 

Advantages:

1.    The ELCB provides a cheap and efficient form of earth leakage protection, particularly in situations where it is difficult to obtain a good earth connection.

2.    All poles of the supply are isolated when an earth fault occurs.

Disadvantages:

1.    The earth continuity conductor to the trip coil may become disconnected.

2.    The complete supply is completely disconnected when a fault occurs in any part of the installation.

3.    The switch mechanism of ELCB can be wedged in the ON position thus allowing dangerous earth fault condition to arise.

 

(C) CHANGE OVER SWITCH

A change over switch - Is a switch, which has got two ways of connections.  When its handle is switched to one of its side the other position will remain ‘off’.  Furthermore, when is switched to the other side (second) the previous position will be off making the second position ‘on’. In other words, a changeover switch is a two-way switch which is used connect two supplies to the same load.

The use of a change over switch, for standby generator.

In normal condition where the power supply from the mains is available that is being connected to an external circuit the standby generators will be ‘off’.  But as soon as there is power failure from the mains a changeover switch is then used to connect the standby generator to the external circuit, leaving the terminals of the main supply off from the external circuit.

The changeover switch must be constructed in such that as the electric power from mains returns back there will be no collision between the phases of the mains and the standby generators.

Job Safety

i.                   Care must be taken when installing a changeover switch.

ii.                A change over switch must be installed in such that only an authorized person can reach

iii.             A change over switch must be installed in a way that it will not operate in potential dangerous situation

 

(D) AN ISOLATOR

It is a mechanical device which is operated manually and used to open or close a circuit of load.

An Isolator switch must be provided close to the supply point so that all equipment can be made safe for maintenance.  Isolators for motor circuits must isolate the motor and the control equipment.

 

(E) MAIN SWITCH

Types of main switch.

i)                   Fused main switch

ii)                MCB’s main switch

The consumer’s main switch is normally interlocked by its cover so that it cannot operate when the switch is open. This is for main switches containing fuses.

For three phase main switch, each phase is connected on an independent fuse.

A main switch must be capable of providing means of isolation, means of supply as well as means of protection of the supply.

In other situations, the main switch is also used as a circuit’s divider in place of a distribution board.

A main switch containing a fuse fulfils these conditions as the switch isolates the supply and the fuse protects the circuit against excess current due to overload or series earth fault.

 

SEQUENCE OF CONTROL EQUIPMENT

The two common methods of controlling the incoming supply. The earth leakage circuit breaker is used where it is difficult to get a good earth path.

(a)             The supply authority’s sealing chamber for the termination of armoured cable. (Service Line)

(b) The supply authority’s fuse and neutral block. (Cutout fuse)

(c)  The supply authority’s energy meter (kWh meter)

(d) The consumer’s Circuit breaker (Earth leakage circuit breaker)

(e)  Consumer’s control unit. (Distribution main switch)

DOMESTIC CONSUMER’S UNIT.

This type of unit is usually made up of the following:

(a) Main switch (63Aor100A) which isolates both the phase and the neutral conductors.

(b) One 30A fuse for cooker circuit

(c) One 30A fuse for ring circuit (13A plug)

(d) 45 fuse for shower unit.

(e) 15A fuse for immersion heater

(f) One or two 5A fuse for lighting circuits.

       Loading of final sub-circuits

 

INSTALL SWITCH GEARS.

Steps:

(a)  Identify tools and materials

(b) Decide whether you want fuses or MCB’S in the 1 phase in consumer unit.

MCB’S are superior to fuses and should be the first choice.

If the fuses are chosen, the first choice should be cartridge fuse, if not available then rewirable fuse.

(c)  Identify the position for mounting switch gears

 Hold the consumer against the wall and mark the positions for the fixing holes hence drill and plug the holes for wood screws.

(d) Before fixing the unit it is better to connect the meter leads and the main earth conductor.

If the fuses are chosen, remove fuse carries from the consumer unit and then mount the consumer unit.

(e)  Draw cable in the consumer’s unit main Switch

(f)   Remove about 30mm of outer sheathing form the ends of the cable and about 25mm of insulation

(g)  Connect the circuit cables to the consume unit terminals according to IEE regulations.

(h) Replace back the fuse carries and covers to consumer’s unit.

(i)    Test for function

(j)    Clean the working area and tools.

 